How often is a Room Integrity Test required?

It is a requirement of British Standards BS EN15004 that any gaseous fire suppression system that protects an enclosure should have a room integrity test when it is commissioned and annually thereafter. It should also be retested if any works are carried out to the building envelope, this can include works such as the installation of a new door or seals and new cables, pipe work or ductwork.

Studies reveal that the predominant cause of failure of gaseous extinguishing systems is poor room sealing. It is also found that room integrity performance reduces with time, usually due to changes in construction, cabling or services or simply by natural movement of the enclosures envelope.


It is important to ensure that good room integrity is established and maintained within areas such as data centre spaces, particularly bearing in mind the potential consequences of system failure.